Description
Technical Specifications
| GENERAL FEATURES | |
| -Only One Unit Required | |
| -Up to Five Indoor Units (3-Port) | |
| -G10 DC Inverter Technology | |
| -Quiet Operation – Both Indoor & Outdoor | |
| -Acrylic Resin Coil Coating | |
| -Intelligent Defrost | |
| -Auto Restart on Power Outages | |
| -Mulit-point Diagnostics | |
| -Unlimited 10 yr Parts Warranty | |
| System Ratings | |
| Non-Ducted Indoor | |
| Rated Cooling Capacity | 24,000 BTUH |
| Cooling Capacity (min-max) | 7,500-33,000 BTUH |
| Rated Heating Capacity | 26,000 BTUH |
| Heating Capacity (min-max) | 7,500-35,000 BTUH |
| SEER/EER | 21/12.5 |
| HSPF/COP | 11/3.7 |
| Ducted Indoor | |
| Rated Cooling Capacity | 24,000 BTUH |
| Cooling Capacity (min-max) | 7,500-33,000 BTUH |
| Rated Heating Capacity | 26,000 BTUH |
| Heating Capacity (min-max) | 7,500-35,000 BTUH |
| SEER/EER | 16.0/10.5 |
| HSPF/COP | 8.5/3.2 |
| Operating Range | |
| Cooling (min-max) | 0 ~ 118°F / -18 ~ 48°C |
| Heating (min-max) | -5 ~ 75°F / -21 ~ 24°C |
| Power Supply | |
| Normal Operational Voltage | 208/230 V, 1 Phase, 60 Hz |
| Voltage Range | 187 – 253 V |
| Main Power Wire Size | 10-2 AWG |
| Interconnecting Cable Wire Size | 14-4 AWG |
| MCA | 23.0 A |
| MOCP/Breaker Size | 30 A |
| Outdoor Unit Data | |
| Compressor | Type: DC Inverter Driven Rotary |
| RLA | 15.8 A |
| Fan Motor | Output Power: 90 W |
| FLA | 0.6 A |
| Air Flow (Max) | 2354 CFM |
| Sound Pressure Level | Cooling: 59 dB(A) |
| Heating: 59 dB(A) | |
| Dimensions & Weights | |
| Unit Dimensions (LxHxD) | 38.6 x 31.1 x 17.3 inch |
| Weight (Net/Shipping) | 152.9/163.9 LBS |
| Min. Number of Indoor Units | 1 |
| Max. Number of Indoor Units | 3 |
| Refrigerant Piping Data | |
| Refrigerant Type | R410A |
| Refrigerant Charge | 77.6 oz |
| Additional Charge Per Line Length | 0.21-oz/ft |
| Connection Method | Flared |
| Factory Charge for Total Line Length | 98-ft |
| Total Refrigerant Pipe Length | 197-ft |
| Max Refrigerant Piping Length to any Indoor Unit | 65-ft |
| Min Refrigerant Piping Length to any Indoor Unit | 10-ft |
| Max Elevation between Indoor Units | 33-ft |
| Max Lift from Outdoor to Indoor Unit | 33-ft |
| Max Drop from Outdoor to Indoor Unit | 33-ft |